Wiring & Application Guide for Three-Phase Delta Systems Using the WEM3080TD Energy Meter

1. What Is a Three-Phase Delta (Δ) Power System?

A three-phase three-wire system, also known as a Delta (Δ) system, is a common type of power distribution method for industrial equipment. It features:

  • No neutral line
  • Three live wires (L1, L2, L3) connected in a triangle (delta) configuration
  • Frequently used in high-power industrial loads such as motors, welders, compressors, and large HVAC systems

Common Voltage Levels (depending on region):

  • 208V (Delta connection)
  • 400V or 415V (common in parts of Europe and Australia)
  • 480V (used in North America for industrial/commercial purposes)

2. Key Characteristics of Delta Power Systems

Feature Description
⚡ Voltage Structure Phase voltage = Line voltage (e.g., L1-L2, L2-L3, L3-L1)
🧰 Typical Use Case Industrial power distribution, 3-phase motor-driven systems
❌ No Neutral Line Cannot directly provide 230V or 120V single-phase loads
⚙️ Balanced Design Stable structure; promotes symmetrical phase voltages

3. Energy Monitoring Challenges in Delta Power Systems

Traditional three-phase energy meters like the WEM3080T rely on measuring each phase’s voltage relative to a neutral line (e.g., L1-N, L2-N, L3-N).
However, Delta systems do not have a neutral line.

❌ Therefore, the WEM3080T is not suitable for 3-phase delta (3-wire) systems.

For accurate monitoring, you must use a meter that supports delta wiring systems
➡️ WEM3080TD Energy Meter


4. Introducing the WEM3080TD: Designed for Delta Power Systems

✅ Key Features:

  • Designed for 3-phase 3-wire Delta systems and dual-phase systems (split-phase)
  • Uses the two-wattmeter method (2 voltage channels + 2 current transformers)
  • Phase B is used as a voltage reference, so no CT is required on B phase

5. Typical Wiring for Three-Phase Delta Systems

Below is the recommended wiring diagram for using the WEM3080TD in a delta system:

WEM3080TD Delta Wiring

Voltage Connections:

  • UA → Line A
  • UB → Line B (used as the voltage reference)
  • UC → Line C

CT (Current Transformer) Installation:

  • CTa → Install on Line A (direction K→L toward the load)
  • CTc → Install on Line C (direction K→L toward the load)
  • CTb → Not used (no current measurement on B phase)

📌 Note: Phase B power readings will always display as 0 — this is expected and correct, as it serves only as a reference line in delta mode.


6. Data Visualization and Platform Support

  • On the IAMMETER-Cloud platform, WEM3080TD calculates total power and energy using the two-wattmeter method
  • Supports real-time charts, historical data analysis, and CSV report export

7. Application Scenarios: Where to Use WEM3080TD

Scenario Type Suitable for WEM3080TD?
3-phase 3-wire Delta system (no neutral) ✅ Yes
3-phase 4-wire Wye system ❌ No (use WEM3080T instead)
Dual-phase (split-phase, 2 hot wires) ✅ Yes
Single-phase system ❌ No

8. Conclusion

If your power system uses a 3-phase 3-wire delta configuration,
the WEM3080TD is the only IAMMETER product specifically designed for accurate energy monitoring in this setup.

With simplified wiring (only 2 CTs required) and full compatibility with IAMMETER’s cloud platform,
it is an ideal solution for industrial and commercial energy management.